Skip to Content

Condenser KA/KB-2x980AB5-B01I C

Condenser KA/KB-2x980AB5-B01I C
Illustrative photo

Producer: Karyer · Line: KA/KB (General)

Product code: KA/KB-2x980AB5-B01I C

Heat rejection i
864.31 kW
Air flow
319,575 m³/h
Fin spacing
2.5 mm
Fans
18 × ⌀800 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 319,575 m³/h
External surface 1,880.4 m²
Inner volume 257.5 dm³
Fin spacing 2.5 mm
Fin materialAluminium
Net weight 2,412 kg
Fans
Quantity 18
Diameter 800 mm
Speed 880 rpm
Power 35,226 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 62.0 dB(A)
Sound power 94.9 dB(A)
Energy class E
Connections
Inlet Ø66,7
Outlet Ø66,7
Defrost
KA/KB-2x980AB5-B01I C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
875.140 kW Refrigerant flow 20,494 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 875.14 880.86 888.79 899.90 915.83 940.80

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 875.140

Dimensions

Dimension drawing of KA/KB-2x980AB5-B01I C
Dimension drawing
Dimensions as drawn
A 11100 mm
B 1350 mm
C 2360 mm
F 1050 mm
G 450 mm
E 10900 mm
H 1200 mm
I 2310 mm
D IN Ø66,7
D OUT Ø66,7
Overall [mm]
Length 11100 mm
Width 2360 mm
Height 1350 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.