Skip to Content

Condenser KA/KB-880AC5-B01I C

Condenser KA/KB-880AC5-B01I C
Illustrative photo

Producer: Karyer · Line: KA/KB (General)

Product code: KA/KB-880AC5-B01I C

Heat rejection i
448.87 kW
Air flow
133,564 m³/h
Fin spacing
2.5 mm
Fans
8 × ⌀800 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 133,564 m³/h
External surface 1,114.3 m²
Inner volume 146.2 dm³
Fin spacing 2.5 mm
Fin materialAluminium
Net weight 1,263 kg
Fans
Quantity 8
Diameter 800 mm
Speed 880 rpm
Power 15,656 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.1 dB(A)
Energy class E
Connections
Inlet Ø54
Outlet Ø42
Defrost
KA/KB-880AC5-B01I C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
454.447 kW Refrigerant flow 10,642 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 454.45 456.12 458.97 463.45 470.38 481.44

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 454.447

Dimensions

Dimension drawing of KA/KB-880AC5-B01I C
Dimension drawing
Dimensions as drawn
A 9900 mm
B 1350 mm
C 1240 mm
F 1050 mm
G 450 mm
E 9700 mm
H 1200 mm
I 1190 mm
D IN Ø54
D OUT Ø42
Overall [mm]
Length 9900 mm
Width 1240 mm
Height 1350 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.