Skip to Content

Condenser KA/KB-980AB1-B01I C

Condenser KA/KB-980AB1-B01I C
Illustrative photo

Producer: Karyer · Line: KA/KB (General)

Product code: KA/KB-980AB1-B01I C

Heat rejection i
467.30 kW
Air flow
156,395 m³/h
Fin spacing
2.1 mm
Fans
9 × ⌀800 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 156,395 m³/h
External surface 1,112.0 m²
Inner volume 128.7 dm³
Fin spacing 2.1 mm
Fin materialAluminium
Net weight 1,349 kg
Fans
Quantity 9
Diameter 800 mm
Speed 880 rpm
Power 17,613 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 90.8 dB(A)
Energy class E
Connections
Inlet Ø66,7
Outlet Ø66,7
Defrost
KA/KB-980AB1-B01I C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
473.137 kW Refrigerant flow 11,080 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 473.14 476.10 480.15 485.81 493.90 506.61

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 473.137

Dimensions

Dimension drawing of KA/KB-980AB1-B01I C
Dimension drawing
Dimensions as drawn
A 11100 mm
B 1350 mm
C 1240 mm
F 1050 mm
G 450 mm
E 10900 mm
H 1200 mm
I 1190 mm
D IN Ø66,7
D OUT Ø66,7
Overall [mm]
Length 11100 mm
Width 1240 mm
Height 1350 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.