Skip to Content

Condenser KA/KB-980AC5-B03 C

Condenser KA/KB-980AC5-B03 C
Illustrative photo

Producer: Karyer · Line: KA/KB (General)

Product code: KA/KB-980AC5-B03 C

Heat rejection i
336.05 kW
Air flow
78,985 m³/h
Fin spacing
2.5 mm
Fans
9 × ⌀800 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: KA/KB — KA = vertical, KB = horizontal industrial condenser.
  • D
    Number of fans per row: 9 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 03 — three-phase 400 V 50 Hz, 12-pole AC fan (in this series)

Data

Coil
Air flow 78,985 m³/h
External surface 1,253.6 m²
Inner volume 163.5 dm³
Fin spacing 2.5 mm
Fin materialAluminium
Net weight 1,314 kg
Fans
Quantity 9
Diameter 800 mm
Speed 435 rpm
Power 2,880 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 41.0 dB(A)
Sound power 73.5 dB(A)
Energy class B
Connections
Inlet Ø54
Outlet Ø42
Defrost
KA/KB-980AC5-B03 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · High speed (Δ)
340.011 kW Refrigerant flow 7,962 kg/h
Heat rejection · Low speed (Y)
257.530 kW Refrigerant flow 6,031 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
High speed (Δ) 340.01 339.84 340.34 341.71 344.29 348.75
Low speed (Y) 257.53 257.01 256.98 257.59 259.04 261.76

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
High speed (Δ) 340.011
Low speed (Y) 257.530

Dimensions

Dimension drawing of KA/KB-980AC5-B03 C
Dimension drawing
Dimensions as drawn
A 11100 mm
B 1350 mm
C 1240 mm
F 1050 mm
G 450 mm
E 10900 mm
H 1200 mm
I 1190 mm
D IN Ø54
D OUT Ø42
Overall [mm]
Length 11100 mm
Width 1240 mm
Height 1350 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.