Skip to Content

Condenser KA/KB-t-2x191LB1-B04I C

Condenser KA/KB-t-2x191LB1-B04I C
Illustrative photo

Producer: Karyer · Line: KA/KB (General)

Product code: KA/KB-t-2x191LB1-B04I C

Heat rejection i
174.77 kW
Air flow
54,394 m³/h
Fin spacing
2.1 mm
Fans
2 × ⌀910 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 54,394 m³/h
External surface 267.9 m²
Inner volume 33.4 dm³
Fin spacing 2.1 mm
Fin materialAluminium
Net weight 381 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 92.9 dB(A)
Energy class E
Connections
Inlet Ø42
Outlet Ø35
Defrost
KA/KB-t-2x191LB1-B04I C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
176.983 kW Refrigerant flow 4,145 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 176.98 177.89 179.25 181.29 184.32 189.10

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 176.983

Dimensions

Dimension drawing of KA/KB-t-2x191LB1-B04I C
Dimension drawing
Dimensions as drawn
A 2050 mm
B 1520 mm
C 2310 mm
F 1050 mm
G 450 mm
E 1850 mm
H 1750 mm
I 2260 mm
D IN Ø42
D OUT Ø35
Overall [mm]
Length 2050 mm
Width 2310 mm
Height 1520 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.