Product code: KA/KB-t-2x750EA5-B09 C

Heat rejection i
242.04 kW
Air flow
102,572 m³/h
Fin spacing
2.5 mm
Fans
14 × ⌀500 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 102,572 m³/h
External surface 351.4 m²
Inner volume 50.6 dm³
Fin spacing 2.5 mm
Fin materialAluminium
Net weight 705 kg
Fans
Quantity 14
Diameter 500 mm
Speed 1,330 rpm
Power 9,940 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet Ø54
Outlet Ø54
Defrost
KA/KB-t-2x750EA5-B09 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
245.140 kW Refrigerant flow 5,741 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 245.14 246.78 249.17 252.63 257.70 265.61

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 245.140

Dimensions

Dimension drawing of KA/KB-t-2x750EA5-B09 C
Dimension drawing
Dimensions as drawn
A 5900 mm
B 1200 mm
C 1710 mm
F 1050 mm
G 450 mm
E 5700 mm
H 800 mm
I 1660 mm
D IN Ø54
D OUT Ø54
Overall [mm]
Length 5900 mm
Width 1800 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.