Skip to Content

Condenser KARBOX 5 CSH-235-C01 C

Condenser KARBOX 5 CSH-235-C01 C
Illustrative photo

Producer: Karyer · Line: KARBOX CSH

Product code: KARBOX 5 CSH-235-C01 C

Heat rejection i
14.01 kW
Air flow
4,506 m³/h
Fin spacing
2.5 mm
Fans
2 × ⌀350 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 4,506 m³/h
External surface 28.3 m²
Inner volume 3.0 dm³
Fin spacing 2.5 mm
Fin materialAluminium
Net weight 85 kg
Fans
Quantity 2
Diameter 350 mm
Speed 1,340 rpm
Power 330 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 42.0 dB(A)
Sound power 73.0 dB(A)
Energy class D
Connections
Inlet Ø19
Outlet Ø15,9
Defrost
KARBOX 5 CSH-235-C01 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
14.185 kW Refrigerant flow 332 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 14.19 14.26 14.38 14.56 14.81 15.21

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 14.185

Dimensions

Dimension drawing of KARBOX 5 CSH-235-C01 C
Dimension drawing
Dimensions as drawn
A 1280 mm
B 1075 mm
C 535 mm
F 605 mm
G 550 mm
E 715 mm
H 455 mm
D 825 mm
D IN Ø19
D OUT Ø15,9
Overall [mm]
Length 1280 mm
Width 715 mm
Height 1075 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.