Condenser KC-191EB1-B04 C

Condenser KC-191EB1-B04 C
Illustrative photo

Producer: Karyer · Line: KC (Dry)

Product code: KC-191EB1-B04 C

Heat rejection i
145.27 kW
Air flow
33,699 m³/h
Fin spacing
2.1 mm
Fans
1 × ⌀910 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 33,699 m³/h
External surface 564.8 m²
Inner volume 64.7 dm³
Fin spacing 2.1 mm
Fin materialAluminium
Net weight 485 kg
Fans
Quantity 1
Diameter 910 mm
Speed 840 rpm
Power 2,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.0 dB(A)
Energy class D
Connections
Inlet Ø28
Outlet Ø28
Defrost
KC-191EB1-B04 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · High speed (Δ)
146.950 kW Refrigerant flow 3,441 kg/h
Heat rejection · Low speed (Y)
117.198 kW Refrigerant flow 2,745 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
High speed (Δ) 146.95 146.54 146.25 146.16 146.35 146.97
Low speed (Y) 117.20 116.60 116.12 115.82 115.76 116.03

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
High speed (Δ) 146.950
Low speed (Y) 117.198

Dimensions

Dimension drawing of KC-191EB1-B04 C
Dimension drawing
Dimensions as drawn
A 1978 mm
B 1150 mm
C 2860 mm
F 1050 mm
E1 2430 mm
D IN Ø28
D OUT Ø28
Overall [mm]
Length 2860 mm
Width 1150 mm
Height 1978 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.