KC-t-563AA1-B19 C
215.54 kW
Defrost: None
Product code: KC-291AC5-B04 C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
How to read the code of this model.
| Air flow | 61,837 m³/h |
|---|---|
| External surface | 477.9 m² |
| Inner volume | 65.5 dm³ |
| Fin spacing | 2.5 mm |
| Fin material | Aluminium |
| Net weight | 596 kg |
| Quantity | 2 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 5,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø35 |
| KC-291AC5-B04 C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| High speed (Δ) | 218.39 | 218.66 | 219.43 | 220.88 | 223.31 | 227.38 |
| Low speed (Y) | 174.89 | 174.86 | 175.23 | 176.13 | 177.78 | 180.67 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| High speed (Δ) | 218.385 |
| Low speed (Y) | 174.890 |
| A | 1978 mm |
|---|---|
| B | 1150 mm |
| C | 2860 mm |
| F | 1050 mm |
| E1 | 1230 mm |
| D IN | Ø42 |
| D OUT | Ø35 |
| Length | 2860 mm |
|---|---|
| Width | 1150 mm |
| Height | 1978 mm |
Our engineers answer with a selection for your conditions.