KC-2x380JB5-B01C C
596.37 kW
Defrost: None
Product code: KC-2x391EC5-C04C C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 170,536 m³/h |
|---|---|
| External surface | 1,400.4 m² |
| Inner volume | 194.9 dm³ |
| Fin spacing | 2.5 mm |
| Fin material | Aluminium |
| Net weight | 1,831 kg |
| Quantity | 6 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 16,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 98.0 dB(A) |
| Energy class | D |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø54 |
| KC-2x391EC5-C04C C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| High speed (Δ) | 604.05 | 606.13 | 609.38 | 614.35 | 621.86 | 634.13 |
| Low speed (Y) | 482.79 | 483.54 | 485.27 | 488.37 | 493.43 | 501.71 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| High speed (Δ) | 604.047 |
| Low speed (Y) | 482.786 |
| A | 2511 mm |
|---|---|
| B | 2300 mm |
| C | 4050 mm |
| F | 2230 mm |
| G | 4300 mm |
| E1 | 1250 mm |
| E2 | 1200 mm |
| D IN | Ø54 |
| D OUT | Ø54 |
| Length | 4050 mm |
|---|---|
| Width | 2300 mm |
| Height | 2511 mm |
Our engineers answer with a selection for your conditions.