KC-t-2x491MB1-B04T C
853.08 kW
Defrost: None
Product code: KC-2x580FB1-B01T C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 228,346 m³/h |
|---|---|
| External surface | 2,513.6 m² |
| Inner volume | 284.6 dm³ |
| Fin spacing | 2.1 mm |
| Fin material | Aluminium |
| Net weight | 2,918 kg |
| Quantity | 10 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 18,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.5 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø42 |
| KC-2x580FB1-B01T C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| High speed (Δ) | 861.32 | 862.47 | 864.96 | 869.43 | 876.86 | 889.94 |
| Low speed (Y) | 683.12 | 682.47 | 682.97 | 685.08 | 689.49 | 697.56 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| High speed (Δ) | 861.316 |
| Low speed (Y) | 683.117 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 6450 mm |
| F | 2330 mm |
| G | 6700 mm |
| E1 | 1250 mm |
| E2 | 3600 mm |
| D IN | Ø42 |
| D OUT | Ø42 |
| Length | 6700 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.