Skip to Content

Condenser KC-2x591AC1-C04C C

Condenser KC-2x591AC1-C04C C
Illustrative photo

Producer: Karyer · Line: KC (Dry)

Product code: KC-2x591AC1-C04C C

Heat rejection i
996.45 kW
Air flow
282,360 m³/h
Fin spacing
2.1 mm
Fans
10 × ⌀910 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 282,360 m³/h
External surface 2,113.7 m²
Inner volume 229.8 dm³
Fin spacing 2.1 mm
Fin materialAluminium
Net weight 2,762 kg
Fans
Quantity 10
Diameter 910 mm
Speed 840 rpm
Power 28,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 100.0 dB(A)
Energy class D
Connections
Inlet Ø54
Outlet Ø42
Defrost
KC-2x591AC1-C04C C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · High speed (Δ)
1008.791 kW Refrigerant flow 23,624 kg/h
Heat rejection · Low speed (Y)
795.907 kW Refrigerant flow 18,638 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
High speed (Δ) 1008.79 1011.09 1015.99 1024.48 1038.27 1060.95
Low speed (Y) 795.91 796.67 799.48 805.04 814.51 830.43

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
High speed (Δ) 1008.791
Low speed (Y) 795.907

Dimensions

Dimension drawing of KC-2x591AC1-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 6450 mm
F 2230 mm
G 6700 mm
E1 1250 mm
E2 3600 mm
D IN Ø54
D OUT Ø42
Overall [mm]
Length 6450 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.