KC-991CD5-B04 C
1159.04 kW
Defrost: None
Product code: KC-2x780FB1-B01T C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 319,684 m³/h |
|---|---|
| External surface | 3,519.1 m² |
| Inner volume | 410.1 dm³ |
| Fin spacing | 2.1 mm |
| Fin material | Aluminium |
| Net weight | 3,987 kg |
| Quantity | 14 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 25,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 92.5 dB(A) |
| Energy class | D |
| Inlet | Ø66,7 |
|---|---|
| Outlet | Ø54 |
| KC-2x780FB1-B01T C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| High speed (Δ) | 1173.80 | 1173.93 | 1177.17 | 1184.63 | 1198.14 | 1221.91 |
| Low speed (Y) | 928.41 | 927.11 | 928.20 | 932.45 | 941.16 | 957.17 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| High speed (Δ) | 1173.802 |
| Low speed (Y) | 928.409 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 8850 mm |
| F | 2330 mm |
| G | 9100 mm |
| E1 | 1250 mm |
| E2 | 1200 mm |
| E3 | 3600 mm |
| D IN | Ø66,7 |
| D OUT | Ø54 |
| Length | 9100 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |