KC-2x780FC5-B01T C
1258.14 kW
Defrost: None
Product code: KC-2x880EB1-B01C C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 355,995 m³/h |
|---|---|
| External surface | 3,457.0 m² |
| Inner volume | 389.9 dm³ |
| Fin spacing | 2.1 mm |
| Fin material | Aluminium |
| Net weight | 4,007 kg |
| Quantity | 16 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 28,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø54 |
| KC-2x880EB1-B01C C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| High speed (Δ) | 1271.32 | 1273.26 | 1278.17 | 1287.21 | 1302.30 | 1327.59 |
| Low speed (Y) | 1008.67 | 1008.45 | 1010.56 | 1015.81 | 1025.59 | 1042.80 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| High speed (Δ) | 1271.324 |
| Low speed (Y) | 1008.665 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 10050 mm |
| F | 2230 mm |
| G | 10300 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| D IN | Ø54 |
| D OUT | Ø54 |
| Length | 10300 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.