Skip to Content

Condenser KC-2x991EC1-C04C C

Condenser KC-2x991EC1-C04C C
Illustrative photo

Producer: Karyer · Line: KC (Dry)

Product code: KC-2x991EC1-C04C C

Heat rejection i
1914.64 kW
Air flow
501,108 m³/h
Fin spacing
2.1 mm
Fans
18 × ⌀910 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: KC — KC = classical V-type industrial condenser.
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 9 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: C — generation C
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
  • K
    Delivery version (optional): C — C: container delivery version

Data

Coil
Air flow 501,108 m³/h
External surface 4,973.7 m²
Inner volume 552.2 dm³
Fin spacing 2.1 mm
Fin materialAluminium
Net weight 5,012 kg
Fans
Quantity 18
Diameter 910 mm
Speed 840 rpm
Power 50,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 71.0 dB(A)
Sound power 104.0 dB(A)
Energy class D
Connections
Inlet Ø66,7
Outlet Ø54
Defrost
KC-2x991EC1-C04C C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · High speed (Δ)
1937.718 kW Refrigerant flow 45,377 kg/h
Heat rejection · Low speed (Y)
1522.146 kW Refrigerant flow 35,645 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
High speed (Δ) 1937.72 1941.70 1949.11 1961.70 1981.46 2014.59
Low speed (Y) 1522.15 1522.60 1525.78 1532.79 1545.26 1566.36

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
High speed (Δ) 1937.718
Low speed (Y) 1522.146

Dimensions

Dimension drawing of KC-2x991EC1-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 11250 mm
F 2230 mm
G 11500 mm
E1 1250 mm
E2 2400 mm
E3 3600 mm
D IN Ø66,7
D OUT Ø54
Overall [mm]
Length 11250 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.