KC-2x380GC5-B01C C
571.97 kW
Defrost: None
Product code: KC-491EB1-B04 C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 134,794 m³/h |
|---|---|
| External surface | 2,259.2 m² |
| Inner volume | 262.8 dm³ |
| Fin spacing | 2.1 mm |
| Fin material | Aluminium |
| Net weight | 1,707 kg |
| Quantity | 4 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 11,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 97.0 dB(A) |
| Energy class | D |
| Inlet | Ø66,7 |
|---|---|
| Outlet | Ø54 |
| KC-491EB1-B04 C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| High speed (Δ) | 578.02 | 575.45 | 574.03 | 574.10 | 576.21 | 581.49 |
| Low speed (Y) | 459.84 | 457.14 | 455.34 | 454.69 | 455.55 | 458.67 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| High speed (Δ) | 578.022 |
| Low speed (Y) | 459.837 |
| A | 1978 mm |
|---|---|
| B | 1150 mm |
| C | 10060 mm |
| F | 1050 mm |
| E1 | 2430 mm |
| E2 | 2400 mm |
| D IN | Ø66,7 |
| D OUT | Ø54 |
| Length | 10060 mm |
|---|---|
| Width | 1150 mm |
| Height | 1978 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.