Skip to Content

KC (Dry)

Refrigerants
R134a, R22, R290, R32, R404A, R407A, R407B, R407C, R407F, R410A, R448A, R449A, R450a, R452a, R454A, R454C, R455A, R507A, R513a
Capacity
28.10–2137.87 kW
Fans
⌀630, ⌀800, ⌀910 mm
Max. working pressure
27 bar
KC (Dry)

Model nomenclature

How to read the model codes of this series, with an example.

  • A
    Series KC = KC = classical V-type industrial condenser.
  • B
    Fin type (optional "t") — = absent: standard corrugated finst = t: louvered fins (high-efficiency fin surface)
  • C
    Fan rows (optional "Nx") — Catalogue: "Fan Row no." (number before x/X). — = absent: 1 fan row2x = 2 fan rows
  • D
    Number of fans per row — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter — Two digits = diameter / 10 (91 = Ø910). 63 = Ø630 mm80 = Ø800 mm91 = Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter) A = 2 tube rowsB = 3 tube rowsC = 4 tube rowsD = 5 tube rows
  • H
    Fin spacing — Catalogue fin-spacing code. 1 = 2.1 mm5 = 2.5 mm
  • I
    Generation code — Catalogue: "Generation Code". B = generation BC = generation C
  • J
    Fan data (fan motor code) — Catalogue: "Fan Data". Two digits select the fan motor (supply, poles); the meaning is series-specific. 01 = fan motor code; supply/poles vary with diameter04 = three-phase 400 V 50 Hz, 6-pole AC fan (in this series)08 = three-phase 400 V 50 Hz, 4-pole AC fan (in this series)19 = three-phase 400 V 50 Hz, 4-pole AC fan (in this series)
  • K
    Delivery version (optional) — = absent: standardC = C: container delivery versionT = T: truck delivery version
Model Heat rejection [kW] i Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 % Fans Air flow [m³/h] Variants
KC-291CD5-B04 C 258.59 kW 2 × ⌀910 59,860
Variants (1)
KC-563AC5-B19 C 260.60 kW 5 × ⌀630 63,789
Variants (1)
KC-663AB5-B19 C 260.78 kW 6 × ⌀630 77,510
Variants (1)
KC-291DC5-B04 C 261.32 kW 2 × ⌀910 65,516
Variants (1)
KC-2x191KB5-B04T C 261.37 kW 2 × ⌀910 67,192
Variants (1)
KC-t-463AB1-B08 C 265.00 kW 4 × ⌀630 66,242
Variants (1)
KC-291AD1-B04 C 265.05 kW 2 × ⌀910 59,196
Variants (1)
KC-380DB5-B01 C 265.11 kW 3 × ⌀800 72,463
Variants (1)
KC-t-663AB1-B01 C 266.24 kW 6 × ⌀630 58,586
Variants (1)
KC-t-663AA1-B19 C 266.29 kW 6 × ⌀630 77,745
Variants (1)
KC-463AC1-B08 C 266.37 kW 4 × ⌀630 65,826
Variants (1)
KC-391AB5-B04 C 267.41 kW 3 × ⌀910 95,433
Variants (1)
KC-t-2x191RB1-B04T C 267.69 kW 2 × ⌀910 64,742
Variants (1)
KC-t-291FC1-B04 C 268.13 kW 2 × ⌀910 59,274
Variants (1)
KC-380CB1-B01 C 269.39 kW 3 × ⌀800 69,641
Variants (1)
KC-t-663AA5-B08 C 269.89 kW 6 × ⌀630 102,721
Variants (1)
KC-291EB5-B04 C 273.09 kW 2 × ⌀910 67,629
Variants (1)
KC-2x280BB5-B01T C 273.36 kW 4 × ⌀800 91,727
Variants (1)
KC-663AC1-B01 C 273.37 kW 6 × ⌀630 58,272
Variants (1)
KC-463AD5-B08 C 274.51 kW 4 × ⌀630 65,138
Variants (1)
KC-291CD1-B04 C 274.56 kW 2 × ⌀910 58,821
Variants (1)
KC-2x191HC1-B04T C 275.31 kW 2 × ⌀910 64,385
Variants (1)
KC-t-380FB1-B01 C 277.72 kW 3 × ⌀800 67,663
Variants (1)
KC-t-563AB5-B08 C 277.98 kW 5 × ⌀630 83,524
Variants (1)
KC-2x280AB1-B01C C 278.23 kW 4 × ⌀800 88,060
Variants (1)
KC-2x191KB1-B04T C 279.42 kW 2 × ⌀910 66,915
Variants (1)
KC-t-291HB1-B04 C 279.72 kW 2 × ⌀910 65,380
Variants (1)
KC-t-563AB1-B19 C 280.09 kW 5 × ⌀630 63,678
Variants (1)
KC-380AC1-B01 C 280.22 kW 3 × ⌀800 67,153
Variants (1)
KC-291DC1-B04 C 284.49 kW 2 × ⌀910 65,085
Variants (1)
KC-563AB1-B08 C 285.88 kW 5 × ⌀630 84,191
Variants (1)
KC-t-463AC5-B08 C 285.96 kW 4 × ⌀630 65,187
Variants (1)
KC-563AC1-B19 C 287.64 kW 5 × ⌀630 63,436
Variants (1)
KC-480AB5-B01 C 287.75 kW 4 × ⌀800 92,846
Variants (1)
KC-380AD5-B01 C 288.07 kW 3 × ⌀800 66,283
Variants (1)
KC-663AB1-B19 C 289.12 kW 6 × ⌀630 77,178
Variants (1)
KC-2x280EB5-B01C C 290.01 kW 4 × ⌀800 90,040
Variants (1)
KC-291EB1-B04 C 291.09 kW 2 × ⌀910 67,397
Variants (1)
KC-t-2x280LB5-B01C C 291.77 kW 4 × ⌀800 86,876
Variants (1)
KC-380DB1-B01 C 292.08 kW 3 × ⌀800 72,206
Variants (1)
KC-663AB5-B08 C 292.43 kW 6 × ⌀630 101,766
Variants (1)
KC-380CC5-B01 C 292.64 kW 3 × ⌀800 68,604
Variants (1)
KC-463AD1-B08 C 293.05 kW 4 × ⌀630 64,451
Variants (1)
KC-t-663AB5-B19 C 295.90 kW 6 × ⌀630 76,813
Variants (1)
KC-t-380HB5-B01 C 296.83 kW 3 × ⌀800 71,922
Variants (1)
KC-t-463AC1-B08 C 297.60 kW 4 × ⌀630 64,504
Variants (1)
KC-391CB5-B04 C 298.73 kW 3 × ⌀910 95,112
Variants (1)
KC-391AB1-B04 C 299.56 kW 3 × ⌀910 94,493
Variants (1)
KC-380AD1-B01 C 304.12 kW 3 × ⌀800 65,411
Variants (1)
KC-2x280AC5-B01C C 304.21 kW 4 × ⌀800 86,037
Variants (1)

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.