Skip to Content

Condenser KC-LF-2x291JC1-B04 C

Condenser KC-LF-2x291JC1-B04 C
Illustrative photo

Producer: Karyer · Line: KC-LF (V-type with chassis)

Product code: KC-LF-2x291JC1-B04 C

Heat rejection i
329.37 kW
Air flow
94,981 m³/h
Fin spacing
2.1 mm
Fans
4 × ⌀910 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 94,981 m³/h
External surface 753.1 m²
Inner volume 90.0 dm³
Fin spacing 2.1 mm
Fin materialAluminium
Net weight 1,197 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 97.1 dB(A)
Energy class E
Connections
Inlet Ø42
Outlet Ø35
Defrost
KC-LF-2x291JC1-B04 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · High speed (Δ)
333.439 kW Refrigerant flow 7,808 kg/h
Heat rejection · Low speed (Y)
not rated

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
High speed (Δ) 333.44 335.09 337.49 341.05 346.24 354.44
Low speed (Y) not rated not rated 259.69 262.00 265.47 270.90

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
High speed (Δ) 333.439
Low speed (Y) —

Dimensions

Dimension drawing of KC-LF-2x291JC1-B04 C
Dimension drawing
Dimensions as drawn
A 2645 mm
B 2300 mm
C 3200 mm
E 950 mm
D IN Ø42
D OUT Ø35
Overall [mm]
Length 3200 mm
Width 2300 mm
Height 2645 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.