Product code: KT-125AD4-B05 C

Heat rejection i
2.33 kW
Air flow
576 m³/h
Fin spacing
3.0 mm
Fans
1 × ⌀250 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 576 m³/h
External surface 5.8 m²
Inner volume 0.7 dm³
Fin spacing 3.0 mm
Fin materialAluminium
Net weight 7 kg
Fans
Quantity 1
Diameter 250 mm
Speed 1,300 rpm
Power 95 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 28.0 dB(A)
Sound power 58.5 dB(A)
Energy class E
Connections
Inlet Ø12
Outlet Ø10
Defrost
KT-125AD4-B05 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
2.362 kW Refrigerant flow 55 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 2.36 2.37 2.38 2.39 2.42 2.46

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 2.362

Dimensions

Dimension drawing of KT-125AD4-B05 C
Dimension drawing
Dimensions as drawn
A 350 mm
B 280 mm
C 175 mm
F 40 mm
G 95 mm
E 336 mm
C1 195 mm
C2 276 mm
D IN Ø12
D OUT Ø10
Overall [mm]
Length 350 mm
Width 276 mm
Height 280 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.