Skip to Content

Condenser KT-145CB2-B03 C

Condenser KT-145CB2-B03 C
Illustrative photo

Producer: Karyer · Line: KT (Commercial)

Product code: KT-145CB2-B03 C

Heat rejection i
11.12 kW
Air flow
4,821 m³/h
Fin spacing
2.5 mm
Fans
1 × ⌀450 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 4,821 m³/h
External surface 21.2 m²
Inner volume 2.2 dm³
Fin spacing 2.5 mm
Fin materialAluminium
Net weight 23 kg
Fans
Quantity 1
Diameter 450 mm
Speed 1,300 rpm
Power 350 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 49.0 dB(A)
Sound power 80.0 dB(A)
Energy class E
Connections
Inlet Ø16
Outlet Ø12
Defrost
KT-145CB2-B03 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
11.263 kW Refrigerant flow 264 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 11.26 11.34 11.45 11.61 11.84 12.22

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 11.263

Dimensions

Dimension drawing of KT-145CB2-B03 C
Dimension drawing
Dimensions as drawn
A 800 mm
B 620 mm
C 220 mm
F 40 mm
G 140 mm
E 736 mm
C1 260 mm
C2 335 mm
D IN Ø16
D OUT Ø12
Overall [mm]
Length 800 mm
Width 335 mm
Height 620 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.