Skip to Content

Condenser KT-150GC3-B09 C

Condenser KT-150GC3-B09 C
Illustrative photo

Producer: Karyer · Line: KT (Commercial)

Product code: KT-150GC3-B09 C

Heat rejection i
18.30 kW
Air flow
6,230 m³/h
Fin spacing
2.8 mm
Fans
1 × ⌀500 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 6,230 m³/h
External surface 33.1 m²
Inner volume 4.3 dm³
Fin spacing 2.8 mm
Fin materialAluminium
Net weight 32 kg
Fans
Quantity 1
Diameter 500 mm
Speed 1,330 rpm
Power 710 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 47.0 dB(A)
Sound power 78.0 dB(A)
Energy class E
Connections
Inlet Ø16
Outlet Ø12
Defrost
KT-150GC3-B09 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
18.527 kW Refrigerant flow 434 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 18.53 18.65 18.81 19.04 19.35 19.83

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 18.527

Dimensions

Dimension drawing of KT-150GC3-B09 C
Dimension drawing
Dimensions as drawn
A 920 mm
B 590 mm
C 250 mm
F 85 mm
G 80 mm
E 856 mm
C1 290 mm
C2 390 mm
D IN Ø16
D OUT Ø12
Overall [mm]
Length 800 mm
Width 390 mm
Height 590 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.