Skip to Content

Condenser KT-150GD1-B08 C

Condenser KT-150GD1-B08 C
Illustrative photo

Producer: Karyer · Line: KT (Commercial)

Product code: KT-150GD1-B08 C

Heat rejection i
19.31 kW
Air flow
4,067 m³/h
Fin spacing
2.1 mm
Fans
1 × ⌀500 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 4,067 m³/h
External surface 67.1 m²
Inner volume 7.0 dm³
Fin spacing 2.1 mm
Fin materialAluminium
Net weight 49 kg
Fans
Quantity 1
Diameter 500 mm
Speed 880 rpm
Power 290 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 38.0 dB(A)
Sound power 69.0 dB(A)
Energy class C
Connections
Inlet Ø19
Outlet Ø16
Defrost
KT-150GD1-B08 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · High speed (Δ)
19.522 kW Refrigerant flow 457 kg/h
Heat rejection · Low speed (Y)
12.661 kW Refrigerant flow 296 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
High speed (Δ) 19.52 19.47 19.44 19.44 19.48 19.56
Low speed (Y) 12.66 12.62 12.59 12.59 12.61 12.66

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
High speed (Δ) 19.522
Low speed (Y) 12.661

Dimensions

Dimension drawing of KT-150GD1-B08 C
Dimension drawing
Dimensions as drawn
A 900 mm
B 740 mm
C 290 mm
F 40 mm
G 210 mm
E 836 mm
C1 330 mm
C2 430 mm
D IN Ø19
D OUT Ø16
Overall [mm]
Length 900 mm
Width 430 mm
Height 740 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.