Skip to Content

Condenser KT-220AD2-B04 C

Condenser KT-220AD2-B04 C
Illustrative photo

Producer: Karyer · Line: KT (Commercial)

Product code: KT-220AD2-B04 C

Heat rejection i
2.58 kW
Air flow
545 m³/h
Fin spacing
2.5 mm
Fans
2 × ⌀200 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 545 m³/h
External surface 8.4 m²
Inner volume 0.8 dm³
Fin spacing 2.5 mm
Fin materialAluminium
Net weight 9 kg
Fans
Quantity 2
Diameter 200 mm
Speed 1,300 rpm
Power 76 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 21.0 dB(A)
Sound power 52.2 dB(A)
Energy class D
Connections
Inlet Ø12
Outlet Ø10
Defrost
KT-220AD2-B04 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
2.613 kW Refrigerant flow 61 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 2.61 2.61 2.60 2.61 2.61 2.63

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 2.613

Dimensions

Dimension drawing of KT-220AD2-B04 C
Dimension drawing
Dimensions as drawn
A 550 mm
B 220 mm
C 175 mm
F 40 mm
G 95 mm
E 536 mm
C1 195 mm
C2 246 mm
D IN Ø12
D OUT Ø10
Overall [mm]
Length 550 mm
Width 201 mm
Height 220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.