KT-240BC1-B01 C
21.08 kW
Defrost: None
Product code: KT-245DC3-B01 C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 7,880 m³/h |
|---|---|
| External surface | 39.2 m² |
| Inner volume | 5.0 dm³ |
| Fin spacing | 2.7 mm |
| Fin material | Aluminium |
| Net weight | 42 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 78.2 dB(A) |
| Energy class | E |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø16 |
| KT-245DC3-B01 C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| Single phase | 21.40 | 21.60 | 21.89 | 22.30 | 22.89 | 23.82 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| Single phase | 21.396 |
| A | 1180 mm |
|---|---|
| B | 530 mm |
| C | 250 mm |
| F | 85 mm |
| G | 80 mm |
| E | 1086 mm |
| C1 | 290 mm |
| C2 | 380 mm |
| D IN | Ø19 |
| D OUT | Ø16 |
| Length | 1180 mm |
|---|---|
| Width | 380 mm |
| Height | 530 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.