Condenser KT-250BB1-B04 C

Condenser KT-250BB1-B04 C
Illustrative photo

Producer: Karyer · Line: KT (Commercial)

Product code: KT-250BB1-B04 C

Heat rejection i
25.23 kW
Air flow
9,180 m³/h
Fin spacing
2.1 mm
Fans
2 × ⌀500 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 9,180 m³/h
External surface 54.3 m²
Inner volume 4.9 dm³
Fin spacing 2.1 mm
Fin materialAluminium
Net weight 55 kg
Fans
Quantity 2
Diameter 500 mm
Speed 910 rpm
Power 600 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 41.0 dB(A)
Sound power 72.0 dB(A)
Energy class D
Connections
Inlet Ø22
Outlet Ø19
Defrost
KT-250BB1-B04 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
25.556 kW Refrigerant flow 598 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 25.56 25.69 25.92 26.25 26.75 27.56

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 25.556

Dimensions

Dimension drawing of KT-250BB1-B04 C
Dimension drawing
Dimensions as drawn
A 1430 mm
B 720 mm
C 220 mm
F 40 mm
G 140 mm
E 1336 mm
C1 260 mm
C2 360 mm
D IN Ø22
D OUT Ø19
Overall [mm]
Length 1430 mm
Width 360 mm
Height 720 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.