Skip to Content

Condenser KT-263AD2-B01 C

Condenser KT-263AD2-B01 C
Illustrative photo

Producer: Karyer · Line: KT (Commercial)

Product code: KT-263AD2-B01 C

Heat rejection i
76.72 kW
Air flow
17,398 m³/h
Fin spacing
2.5 mm
Fans
2 × ⌀630 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 17,398 m³/h
External surface 237.0 m²
Inner volume 30.0 dm³
Fin spacing 2.5 mm
Fin materialAluminium
Net weight 178 kg
Fans
Quantity 2
Diameter 630 mm
Speed 860 rpm
Power 1,200 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 46.0 dB(A)
Sound power 77.3 dB(A)
Energy class C
Connections
Inlet Ø35
Outlet Ø35
Defrost
KT-263AD2-B01 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
77.604 kW Refrigerant flow 1,817 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 77.60 77.36 77.23 77.27 77.53 78.12

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 77.604

Dimensions

Dimension drawing of KT-263AD2-B01 C
Dimension drawing
Dimensions as drawn
A 2130 mm
B 1220 mm
C 350 mm
F 40 mm
G 270 mm
E 2036 mm
C1 410 mm
C2 475 mm
D IN Ø35
D OUT Ø35
Overall [mm]
Length 2130 mm
Width 510 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.