Skip to Content

Condenser KT-2x245EA2-B01 C

Condenser KT-2x245EA2-B01 C
Illustrative photo

Producer: Karyer · Line: KT (Commercial)

Product code: KT-2x245EA2-B01 C

Heat rejection i
43.98 kW
Air flow
25,444 m³/h
Fin spacing
2.5 mm
Fans
4 × ⌀450 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 25,444 m³/h
External surface 75.3 m²
Inner volume 8.6 dm³
Fin spacing 2.5 mm
Fin materialAluminium
Net weight 95 kg
Fans
Quantity 4
Diameter 450 mm
Speed 1,310 rpm
Power 1,960 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 50.0 dB(A)
Sound power 81.0 dB(A)
Energy class E
Connections
Inlet Ø28
Outlet Ø22
Defrost
KT-2x245EA2-B01 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
44.543 kW Refrigerant flow 1,043 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 44.54 44.89 45.38 46.06 47.03 48.50

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 44.543

Dimensions

Dimension drawing of KT-2x245EA2-B01 C
Dimension drawing
Dimensions as drawn
A 1700 mm
B 1460 mm
C 220 mm
F 40 mm
G 140 mm
E 1636 mm
C1 260 mm
C2 350 mm
D IN Ø28
D OUT Ø22
Overall [mm]
Length 1700 mm
Width 350 mm
Height 1460 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.