KT-t-350HC1-B09 C
74.76 kW
Defrost: None
Product code: KT-2x250HC2-B08 C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 18,934 m³/h |
|---|---|
| External surface | 213.3 m² |
| Inner volume | 28.5 dm³ |
| Fin spacing | 2.5 mm |
| Fin material | Aluminium |
| Net weight | 169 kg |
| Quantity | 4 |
|---|---|
| Diameter | 500 mm |
| Speed | 880 rpm |
| Power | 1,160 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø28 |
| KT-2x250HC2-B08 C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| High speed (Δ) | 75.34 | 75.33 | 75.47 | 75.82 | 76.45 | 77.55 |
| Low speed (Y) | 52.84 | 52.75 | 52.76 | 52.92 | 53.26 | 53.90 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| High speed (Δ) | 75.344 |
| Low speed (Y) | 52.839 |
| A | 1630 mm |
|---|---|
| B | 1860 mm |
| C | 250 mm |
| F | 40 mm |
| G | 170 mm |
| E | 1536 mm |
| C1 | 290 mm |
| C2 | 390 mm |
| D IN | Ø35 |
| D OUT | Ø28 |
| Length | 1630 mm |
|---|---|
| Width | 390 mm |
| Height | 1320 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.