Skip to Content

Condenser KT-363AD2-B01 C

Condenser KT-363AD2-B01 C
Illustrative photo

Producer: Karyer · Line: KT (Commercial)

Product code: KT-363AD2-B01 C

Heat rejection i
110.48 kW
Air flow
25,392 m³/h
Fin spacing
2.5 mm
Fans
3 × ⌀630 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 25,392 m³/h
External surface 324.6 m²
Inner volume 41.4 dm³
Fin spacing 2.5 mm
Fin materialAluminium
Net weight 243 kg
Fans
Quantity 3
Diameter 630 mm
Speed 860 rpm
Power 1,800 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 48.0 dB(A)
Sound power 79.2 dB(A)
Energy class D
Connections
Inlet Ø42
Outlet Ø35
Defrost
KT-363AD2-B01 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
111.761 kW Refrigerant flow 2,617 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 111.76 111.49 111.40 111.55 112.02 112.98

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 111.761

Dimensions

Dimension drawing of KT-363AD2-B01 C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 1220 mm
C 350 mm
F 40 mm
G 270 mm
E 2776 mm
C1 410 mm
C2 475 mm
D IN Ø42
D OUT Ø35
Overall [mm]
Length 2880 mm
Width 510 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.