KT-2x230AC2-B01 C
15.35 kW
Defrost: None
Product code: KT-t-240CB2-B03 C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 4,492 m³/h |
|---|---|
| External surface | 30.2 m² |
| Inner volume | 2.8 dm³ |
| Fin spacing | 2.5 mm |
| Fin material | Aluminium |
| Net weight | 31 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 870 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 36.0 dB(A) |
|---|---|
| Sound power | 67.5 dB(A) |
| Energy class | D |
| Inlet | Ø16 |
|---|---|
| Outlet | Ø12 |
| KT-t-240CB2-B03 C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| Single phase | 15.53 | 15.61 | 15.72 | 15.87 | 16.10 | 16.44 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| Single phase | 15.527 |
| A | 1300 mm |
|---|---|
| B | 520 mm |
| C | 190 mm |
| F | 40 mm |
| G | 110 mm |
| E | 1236 mm |
| C1 | 230 mm |
| C2 | 335 mm |
| D IN | Ø16 |
| D OUT | Ø12 |
| Length | 1100 mm |
|---|---|
| Width | 365 mm |
| Height | 620 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.