Skip to Content

Condenser KT-t-245EC3-B04 C

Condenser KT-t-245EC3-B04 C
Illustrative photo

Producer: Karyer · Line: KT (Commercial)

Product code: KT-t-245EC3-B04 C

Heat rejection i
21.43 kW
Air flow
5,076 m³/h
Fin spacing
2.7 mm
Fans
2 × ⌀450 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 5,076 m³/h
External surface 43.8 m²
Inner volume 5.5 dm³
Fin spacing 2.7 mm
Fin materialAluminium
Net weight 41 kg
Fans
Quantity 2
Diameter 450 mm
Speed 900 rpm
Power 380 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 38.0 dB(A)
Sound power 69.4 dB(A)
Energy class D
Connections
Inlet Ø19
Outlet Ø16
Defrost
KT-t-245EC3-B04 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
21.685 kW Refrigerant flow 508 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 21.69 21.77 21.89 22.06 22.31 22.68

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 21.685

Dimensions

Dimension drawing of KT-t-245EC3-B04 C
Dimension drawing
Dimensions as drawn
A 1180 mm
B 590 mm
C 250 mm
F 85 mm
G 80 mm
E 1086 mm
C1 290 mm
C2 365 mm
D IN Ø19
D OUT Ø16
Overall [mm]
Length 1180 mm
Width 365 mm
Height 590 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.