Skip to Content

Condenser KT-t-2x350FB1-B09 C

Condenser KT-t-2x350FB1-B09 C
Illustrative photo

Producer: Karyer · Line: KT (Commercial)

Product code: KT-t-2x350FB1-B09 C

Heat rejection i
125.54 kW
Air flow
36,573 m³/h
Fin spacing
2.1 mm
Fans
6 × ⌀500 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 36,573 m³/h
External surface 198.3 m²
Inner volume 22.2 dm³
Fin spacing 2.1 mm
Fin materialAluminium
Net weight 192 kg
Fans
Quantity 6
Diameter 500 mm
Speed 1,330 rpm
Power 4,260 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class E
Connections
Inlet Ø35
Outlet Ø28
Defrost
KT-t-2x350FB1-B09 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
127.024 kW Refrigerant flow 2,975 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 127.02 127.86 128.89 130.23 132.05 134.70

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 127.024

Dimensions

Dimension drawing of KT-t-2x350FB1-B09 C
Dimension drawing
Dimensions as drawn
A 2380 mm
B 1320 mm
C 250 mm
F 40 mm
G 170 mm
E 2286 mm
C1 290 mm
C2 390 mm
D IN Ø35
D OUT Ø28
Overall [mm]
Length 2380 mm
Width 390 mm
Height 1320 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.