KT-2x363AD2-B19 C
243.60 kW
Defrost: None
Product code: KT-t-2x363AC2-B19 C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 64,257 m³/h |
|---|---|
| External surface | 405.3 m² |
| Inner volume | 56.8 dm³ |
| Fin spacing | 2.5 mm |
| Fin material | Aluminium |
| Net weight | 358 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 7,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø42 |
| KT-t-2x363AC2-B19 C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| High speed (Δ) | 248.93 | 249.23 | 250.09 | 251.69 | 254.35 | 258.76 |
| Low speed (Y) | 202.96 | 203.30 | 204.05 | 205.39 | 207.54 | 211.02 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| High speed (Δ) | 248.932 |
| Low speed (Y) | 202.955 |
| A | 2990 mm |
|---|---|
| B | 1860 mm |
| C | 320 mm |
| F | 40 mm |
| G | 240 mm |
| E | 2886 mm |
| C1 | 380 mm |
| C2 | 490 mm |
| D IN | Ø54 |
| D OUT | Ø42 |
| Length | 2990 mm |
|---|---|
| Width | 480 mm |
| Height | 1820 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.