KT-t-2x250GB2-B04 C
59.34 kW
Defrost: None
Product code: KT-t-363AB2-B03 C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 13,037 m³/h |
|---|---|
| External surface | 194.8 m² |
| Inner volume | 25.1 dm³ |
| Fin spacing | 2.5 mm |
| Fin material | Aluminium |
| Net weight | 184 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 430 rpm |
| Power | 390 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 28.0 dB(A) |
|---|---|
| Sound power | 59.7 dB(A) |
| Energy class | B |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø28 |
| KT-t-363AB2-B03 C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| High speed (Δ) | 60.07 | 59.94 | 59.84 | 59.78 | 59.80 | 59.93 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| High speed (Δ) | 60.068 |
| A | 2880 mm |
|---|---|
| B | 1220 mm |
| C | 320 mm |
| F | 40 mm |
| G | 240 mm |
| E | 2776 mm |
| C1 | 380 mm |
| C2 | 490 mm |
| D IN | Ø35 |
| D OUT | Ø28 |
| Length | 2880 mm |
|---|---|
| Width | 480 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.