BC/BD-150DA5-B09 C
12.46 kW
Defrost: None
Product code: BC/BD-150BA5-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 7,455 m³/h |
|---|---|
| External surface | 25.4 m² |
| Inner volume | 3.8 dm³ |
| Fin material | Aluminium |
| Net weight | 93 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 700 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 79.0 dB(A) |
| Energy class | E |
| Inlet | 1" |
|---|---|
| Outlet | 1" |
| BC/BD-150BA5-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 6.92 | not rated | not rated | not rated | not rated | not rated |
| 40 | 12.57 | 6.99 | not rated | not rated | not rated | not rated |
| 45 | 18.12 | 12.61 | 7.05 | not rated | not rated | not rated |
| 50 | 23.65 | 18.15 | 12.65 | 7.10 | not rated | not rated |
| 55 | 29.16 | 23.65 | 18.17 | 12.69 | 7.15 | not rated |
| 60 | 34.67 | 29.15 | 23.66 | 18.19 | 12.72 | 7.19 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 12.570 | 2.18 | 40.9 |
| A | 1150 mm |
|---|---|
| B | 1220 mm |
| C | 930 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 900 mm |
| H | 800 mm |
| I | 880 mm |
| K | 1400 mm |
| D IN | 1" |
| D OUT | 1" |
| Length | 1150 mm |
|---|---|
| Width | 960 mm |
| Height | 1220 mm |