BC/BD-163CA5-B01 C
17.60 kW
Defrost: None
Product code: BC/BD-150CD5-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 5,905 m³/h |
|---|---|
| External surface | 67.3 m² |
| Inner volume | 9.1 dm³ |
| Fin material | Aluminium |
| Net weight | 111 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 700 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 78.2 dB(A) |
| Energy class | E |
| Inlet | 1" |
|---|---|
| Outlet | 1" |
| BC/BD-150CD5-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 8.31 | not rated | not rated | not rated | not rated | not rated |
| 40 | 17.47 | 8.77 | not rated | not rated | not rated | not rated |
| 45 | 25.81 | 17.65 | 9.11 | not rated | not rated | not rated |
| 50 | 33.99 | 25.92 | 17.82 | 9.38 | not rated | not rated |
| 55 | 42.10 | 34.04 | 26.02 | 17.97 | 9.61 | not rated |
| 60 | 50.17 | 42.10 | 34.10 | 26.13 | 18.11 | 9.81 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 17.466 | 3.03 | 7.1 |
| A | 950 mm |
|---|---|
| B | 1200 mm |
| C | 920 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 750 mm |
| H | 650 mm |
| I | 870 mm |
| K | 1250 mm |
| D IN | 1" |
| D OUT | 1" |
| Length | 1250 mm |
|---|---|
| Width | 920 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.