BC/BD-2X150BB1-B09 C
36.16 kW
Defrost: None
Product code: BC/BD-163BD5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 11,061 m³/h |
|---|---|
| External surface | 98.5 m² |
| Inner volume | 14.6 dm³ |
| Fin material | Aluminium |
| Net weight | 137 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 1,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-163BD5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 21.20 | not rated | not rated | not rated | not rated | not rated |
| 40 | 36.14 | 21.25 | not rated | not rated | not rated | not rated |
| 45 | 50.72 | 36.10 | 21.30 | not rated | not rated | not rated |
| 50 | 65.19 | 50.60 | 36.07 | 21.35 | not rated | not rated |
| 55 | 79.60 | 64.98 | 50.49 | 36.05 | 21.40 | not rated |
| 60 | 93.98 | 79.31 | 64.81 | 50.42 | 36.07 | 21.47 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 17.78 | not rated | not rated | not rated | not rated | not rated |
| 40 | 30.12 | 17.82 | not rated | not rated | not rated | not rated |
| 45 | 42.14 | 30.08 | 17.86 | not rated | not rated | not rated |
| 50 | 54.05 | 42.03 | 30.05 | 17.90 | not rated | not rated |
| 55 | 65.92 | 53.87 | 41.94 | 30.04 | 17.95 | not rated |
| 60 | 77.76 | 65.67 | 53.73 | 41.89 | 30.06 | 18.02 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 36.142 | 6.27 | 84.4 |
| Low speed (Y) | 30.118 | 5.23 | 61.1 |
| A | 1250 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1000 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 1500 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 1250 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.