Skip to Content

Dry cooler BC/BD-163CB5-B19 C

Dry cooler BC/BD-163CB5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-163CB5-B19 C

Heat rejection i
27.05 kW
Air flow
11,777 m³/h
Fans
1 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 11,777 m³/h
External surface 78.4 m²
Inner volume 11.1 dm³
Fin materialAluminium
Net weight 139 kg
Fans
Quantity 1
Diameter 630 mm
Speed 1,330 rpm
Power 1,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 52.0 dB(A)
Sound power 84.0 dB(A)
Energy class E
Connections
Inlet 1"
Outlet 1"
Defrost
BC/BD-163CB5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
27.049 kW Fluid flow 4.70 m³/h Pressure drop 20.0 kPa
Heat rejection · Low speed (Y)
23.380 kW Fluid flow 4.06 m³/h Pressure drop 15.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 14.15 not rated not rated not rated not rated not rated
40 27.05 14.44 not rated not rated not rated not rated
45 39.54 27.20 14.68 not rated not rated not rated
50 51.93 39.61 27.33 14.88 not rated not rated
55 64.27 51.93 39.67 27.46 15.06 not rated
60 76.58 64.20 51.93 39.74 27.57 15.22

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 12.26 not rated not rated not rated not rated not rated
40 23.38 12.52 not rated not rated not rated not rated
45 34.09 23.51 12.74 not rated not rated not rated
50 44.68 34.14 23.62 12.92 not rated not rated
55 55.23 44.67 34.19 23.73 13.08 not rated
60 65.75 55.16 44.67 34.25 23.83 13.23

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 27.049 4.70 20.0
Low speed (Y) 23.380 4.06 15.3

Dimensions

Dimension drawing of BC/BD-163CB5-B19 C
Dimension drawing
Dimensions as drawn
A 1200 mm
B 1200 mm
C 1240 mm
F 1050 mm
G 450 mm
E 1000 mm
H 900 mm
I 1190 mm
K 1500 mm
D IN 1"
D OUT 1"
Overall [mm]
Length 1500 mm
Width 1240 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.