BC/BD-163BC5-B01 C
25.66 kW
Defrost: None
Product code: BC/BD-163CC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 8,342 m³/h |
|---|---|
| External surface | 104.3 m² |
| Inner volume | 13.8 dm³ |
| Fin material | Aluminium |
| Net weight | 148 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 74.1 dB(A) |
| Energy class | D |
| Inlet | 1" |
|---|---|
| Outlet | 1" |
| BC/BD-163CC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 13.57 | not rated | not rated | not rated | not rated | not rated |
| 40 | 25.61 | 13.87 | not rated | not rated | not rated | not rated |
| 45 | 37.05 | 25.73 | 14.12 | not rated | not rated | not rated |
| 50 | 48.34 | 37.08 | 25.84 | 14.32 | not rated | not rated |
| 55 | 59.55 | 48.28 | 37.11 | 25.94 | 14.51 | not rated |
| 60 | 70.72 | 59.42 | 48.24 | 37.15 | 26.05 | 14.68 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 25.609 | 4.44 | 16.1 |
| A | 1200 mm |
|---|---|
| B | 1200 mm |
| C | 1240 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1000 mm |
| H | 900 mm |
| I | 1190 mm |
| K | 1500 mm |
| D IN | 1" |
| D OUT | 1" |
| Length | 1500 mm |
|---|---|
| Width | 1240 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.