Skip to Content

Dry cooler BC/BD-180AC1-B01 C

Dry cooler BC/BD-180AC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-180AC1-B01 C

Heat rejection i
51.80 kW
Air flow
16,370 m³/h
Fans
1 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 16,370 m³/h
External surface 164.7 m²
Inner volume 20.6 dm³
Fin materialAluminium
Net weight 212 kg
Fans
Quantity 1
Diameter 800 mm
Speed 900 rpm
Power 1,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 50.0 dB(A)
Sound power 81.5 dB(A)
Energy class E
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
BC/BD-180AC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
51.798 kW Fluid flow 8.99 m³/h Pressure drop 39.8 kPa
Heat rejection · Low speed (Y)
40.821 kW Fluid flow 7.08 m³/h Pressure drop 26.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 29.54 not rated not rated not rated not rated not rated
40 51.80 29.77 not rated not rated not rated not rated
45 73.48 51.91 29.98 not rated not rated not rated
50 94.98 73.49 52.02 30.17 not rated not rated
55 116.38 94.89 73.52 52.14 30.37 not rated
60 137.74 116.21 94.85 73.60 52.31 30.58

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 23.52 not rated not rated not rated not rated not rated
40 40.82 23.70 not rated not rated not rated not rated
45 57.60 40.89 23.86 not rated not rated not rated
50 74.20 57.58 40.97 24.02 not rated not rated
55 90.73 74.11 57.59 41.07 24.18 not rated
60 107.21 90.57 74.07 57.65 41.19 24.35

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 51.798 8.99 39.8
Low speed (Y) 40.821 7.08 26.0

Dimensions

Dimension drawing of BC/BD-180AC1-B01 C
Dimension drawing
Dimensions as drawn
A 1550 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 1300 mm
H 1200 mm
I 1190 mm
K 1850 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 1550 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.