BC/BD-2X150DB5-B09 C
32.55 kW
Defrost: None
Product code: BC/BD-180AD1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 7,604 m³/h |
|---|---|
| External surface | 205.9 m² |
| Inner volume | 24.0 dm³ |
| Fin material | Aluminium |
| Net weight | 220 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 32.0 dB(A) |
|---|---|
| Sound power | 64.0 dB(A) |
| Energy class | C |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| BC/BD-180AD1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 19.90 | not rated | not rated | not rated | not rated | not rated |
| 40 | 32.59 | 19.93 | not rated | not rated | not rated | not rated |
| 45 | 44.89 | 32.54 | 19.96 | not rated | not rated | not rated |
| 50 | 57.06 | 44.77 | 32.50 | 19.99 | not rated | not rated |
| 55 | 69.17 | 56.88 | 44.67 | 32.49 | 20.05 | not rated |
| 60 | 81.25 | 68.92 | 56.72 | 44.62 | 32.53 | 20.14 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 14.83 | not rated | not rated | not rated | not rated | not rated |
| 40 | 24.00 | 14.87 | not rated | not rated | not rated | not rated |
| 45 | 32.86 | 23.98 | 14.90 | not rated | not rated | not rated |
| 50 | 41.63 | 32.80 | 23.97 | 14.95 | not rated | not rated |
| 55 | 50.35 | 41.53 | 32.77 | 24.00 | 15.01 | not rated |
| 60 | 59.04 | 50.22 | 41.47 | 32.78 | 24.06 | 15.11 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 32.594 | 5.65 | 51.6 |
| Low speed (Y) | 23.999 | 4.16 | 30.0 |
| A | 1550 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1300 mm |
| H | 1200 mm |
| I | 1190 mm |
| K | 1850 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 1850 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.