BC/BD-t-2X163AC1-B01 C
64.73 kW
Defrost: None
Product code: BC/BD-180CC1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 19,025 m³/h |
|---|---|
| External surface | 239.9 m² |
| Inner volume | 29.7 dm³ |
| Fin material | Aluminium |
| Net weight | 251 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 80.1 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-180CC1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 37.41 | not rated | not rated | not rated | not rated | not rated |
| 40 | 64.78 | 37.61 | not rated | not rated | not rated | not rated |
| 45 | 91.40 | 64.78 | 37.78 | not rated | not rated | not rated |
| 50 | 117.76 | 91.24 | 64.79 | 37.94 | not rated | not rated |
| 55 | 144.01 | 117.44 | 91.10 | 64.82 | 38.10 | not rated |
| 60 | 170.20 | 143.55 | 117.19 | 91.02 | 64.90 | 38.29 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 29.48 | not rated | not rated | not rated | not rated | not rated |
| 40 | 50.51 | 29.62 | not rated | not rated | not rated | not rated |
| 45 | 70.89 | 50.47 | 29.74 | not rated | not rated | not rated |
| 50 | 91.04 | 70.69 | 50.44 | 29.86 | not rated | not rated |
| 55 | 111.09 | 90.71 | 70.55 | 50.45 | 29.98 | not rated |
| 60 | 131.07 | 110.63 | 90.45 | 70.46 | 50.50 | 30.13 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 64.781 | 11.24 | 35.8 |
| Low speed (Y) | 50.514 | 8.76 | 22.9 |
| A | 2100 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1850 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 2400 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2100 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.