BC/BD-350CA1-B09 C
40.10 kW
Defrost: None
Product code: BC/BD-180CD1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 9,047 m³/h |
|---|---|
| External surface | 300.3 m² |
| Inner volume | 33.7 dm³ |
| Fin material | Aluminium |
| Net weight | 266 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 32.0 dB(A) |
|---|---|
| Sound power | 64.0 dB(A) |
| Energy class | B |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| BC/BD-180CD1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 24.61 | not rated | not rated | not rated | not rated | not rated |
| 40 | 39.98 | 24.58 | not rated | not rated | not rated | not rated |
| 45 | 54.86 | 39.81 | 24.56 | not rated | not rated | not rated |
| 50 | 69.58 | 54.57 | 39.68 | 24.56 | not rated | not rated |
| 55 | 84.22 | 69.17 | 54.34 | 39.59 | 24.59 | not rated |
| 60 | 98.83 | 83.71 | 68.85 | 54.17 | 39.56 | 24.65 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 18.73 | not rated | not rated | not rated | not rated | not rated |
| 40 | 30.11 | 18.70 | not rated | not rated | not rated | not rated |
| 45 | 41.11 | 29.96 | 18.67 | not rated | not rated | not rated |
| 50 | 51.99 | 40.86 | 29.84 | 18.66 | not rated | not rated |
| 55 | 62.81 | 51.65 | 40.66 | 29.76 | 18.67 | not rated |
| 60 | 73.60 | 62.38 | 51.37 | 40.52 | 29.72 | 18.71 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 39.977 | 6.93 | 44.1 |
| Low speed (Y) | 30.113 | 5.22 | 26.6 |
| A | 2100 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1850 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 2400 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 2400 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.