BC/BD-150BD1-B09 C
23.39 kW
Defrost: None
Product code: BC/BD-180HB5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 8,639 m³/h |
|---|---|
| External surface | 68.8 m² |
| Inner volume | 8.9 dm³ |
| Fin material | Aluminium |
| Net weight | 175 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 32.0 dB(A) |
|---|---|
| Sound power | 64.0 dB(A) |
| Energy class | C |
| Inlet | 1" |
|---|---|
| Outlet | 1" |
| BC/BD-180HB5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 13.34 | not rated | not rated | not rated | not rated | not rated |
| 40 | 23.34 | 13.44 | not rated | not rated | not rated | not rated |
| 45 | 33.11 | 23.39 | 13.52 | not rated | not rated | not rated |
| 50 | 42.81 | 33.13 | 23.44 | 13.60 | not rated | not rated |
| 55 | 52.47 | 42.79 | 33.15 | 23.50 | 13.68 | not rated |
| 60 | 62.11 | 52.42 | 42.79 | 33.19 | 23.57 | 13.77 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 10.70 | not rated | not rated | not rated | not rated | not rated |
| 40 | 18.62 | 10.78 | not rated | not rated | not rated | not rated |
| 45 | 26.32 | 18.65 | 10.84 | not rated | not rated | not rated |
| 50 | 33.96 | 26.32 | 18.68 | 10.91 | not rated | not rated |
| 55 | 41.57 | 33.93 | 26.33 | 18.72 | 10.97 | not rated |
| 60 | 49.16 | 41.52 | 33.92 | 26.36 | 18.78 | 11.04 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 23.341 | 4.05 | 46.3 |
| Low speed (Y) | 18.615 | 3.23 | 30.9 |
| A | 1400 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1150 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 1700 mm |
| D IN | 1" |
| D OUT | 1" |
| Length | 1700 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.