BC/BD-t-180JB1-B03 C
39.64 kW
Defrost: None
Product code: BC/BD-180MC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 10,409 m³/h |
|---|---|
| External surface | 210.2 m² |
| Inner volume | 26.2 dm³ |
| Fin material | Aluminium |
| Net weight | 264 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 32.0 dB(A) |
|---|---|
| Sound power | 64.0 dB(A) |
| Energy class | B |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| BC/BD-180MC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 23.80 | not rated | not rated | not rated | not rated | not rated |
| 40 | 39.56 | 23.78 | not rated | not rated | not rated | not rated |
| 45 | 54.89 | 39.41 | 23.77 | not rated | not rated | not rated |
| 50 | 70.09 | 54.62 | 39.27 | 23.76 | not rated | not rated |
| 55 | 85.22 | 69.71 | 54.39 | 39.18 | 23.77 | not rated |
| 60 | 100.32 | 84.73 | 69.38 | 54.21 | 39.12 | 23.80 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 18.99 | not rated | not rated | not rated | not rated | not rated |
| 40 | 31.35 | 18.98 | not rated | not rated | not rated | not rated |
| 45 | 43.35 | 31.22 | 18.97 | not rated | not rated | not rated |
| 50 | 55.23 | 43.13 | 31.12 | 18.96 | not rated | not rated |
| 55 | 67.06 | 54.92 | 42.94 | 31.04 | 18.97 | not rated |
| 60 | 78.86 | 66.67 | 54.66 | 42.80 | 30.99 | 19.00 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 39.557 | 6.86 | 55.1 |
| Low speed (Y) | 31.347 | 5.44 | 36.4 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 1180 mm |
| K | 3050 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 3050 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.