BC/BD-t-2X163AC5-B19 C
77.13 kW
Defrost: None
Product code: BC/BD-191BC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 24,395 m³/h |
|---|---|
| External surface | 239.9 m² |
| Inner volume | 29.7 dm³ |
| Fin material | Aluminium |
| Net weight | 256 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-191BC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 44.16 | not rated | not rated | not rated | not rated | not rated |
| 40 | 77.05 | 44.42 | not rated | not rated | not rated | not rated |
| 45 | 109.14 | 77.11 | 44.65 | not rated | not rated | not rated |
| 50 | 140.96 | 109.02 | 77.18 | 44.87 | not rated | not rated |
| 55 | 172.64 | 140.67 | 108.94 | 77.27 | 45.09 | not rated |
| 60 | 204.26 | 172.20 | 140.45 | 108.92 | 77.41 | 45.34 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 34.96 | not rated | not rated | not rated | not rated | not rated |
| 40 | 60.35 | 35.16 | not rated | not rated | not rated | not rated |
| 45 | 85.02 | 60.38 | 35.34 | not rated | not rated | not rated |
| 50 | 109.44 | 84.89 | 60.42 | 35.51 | not rated | not rated |
| 55 | 133.75 | 109.19 | 84.82 | 60.49 | 35.70 | not rated |
| 60 | 158.00 | 133.37 | 109.01 | 84.81 | 60.61 | 35.90 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 77.053 | 13.37 | 48.7 |
| Low speed (Y) | 60.354 | 10.47 | 31.5 |
| A | 2100 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1850 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 2400 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2400 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |