BC/BD-2X163BB1-B19 C
59.41 kW
Defrost: None
Product code: BC/BD-191EB1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 23,941 m³/h |
|---|---|
| External surface | 143.9 m² |
| Inner volume | 17.8 dm³ |
| Fin material | Aluminium |
| Net weight | 217 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-191EB1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 33.67 | not rated | not rated | not rated | not rated | not rated |
| 40 | 59.47 | 33.89 | not rated | not rated | not rated | not rated |
| 45 | 84.79 | 59.58 | 34.09 | not rated | not rated | not rated |
| 50 | 109.96 | 84.81 | 59.70 | 34.28 | not rated | not rated |
| 55 | 135.05 | 109.89 | 84.86 | 59.83 | 34.47 | not rated |
| 60 | 160.11 | 134.90 | 109.87 | 84.94 | 59.99 | 34.66 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 27.31 | not rated | not rated | not rated | not rated | not rated |
| 40 | 47.83 | 27.49 | not rated | not rated | not rated | not rated |
| 45 | 67.90 | 47.92 | 27.66 | not rated | not rated | not rated |
| 50 | 87.83 | 67.91 | 48.01 | 27.81 | not rated | not rated |
| 55 | 107.70 | 87.77 | 67.95 | 48.12 | 27.96 | not rated |
| 60 | 127.53 | 107.57 | 87.75 | 68.02 | 48.25 | 28.13 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 59.468 | 10.32 | 94.4 |
| Low speed (Y) | 47.828 | 8.30 | 64.2 |
| A | 1750 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1500 mm |
| H | 1400 mm |
| I | 1190 mm |
| K | 2050 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2050 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.