Skip to Content

Dry cooler BC/BD-191EB1-B04 C

Dry cooler BC/BD-191EB1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-191EB1-B04 C

Heat rejection i
59.47 kW
Air flow
23,941 m³/h
Fans
1 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • D
    Number of fans per row: 1 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 23,941 m³/h
External surface 143.9 m²
Inner volume 17.8 dm³
Fin materialAluminium
Net weight 217 kg
Fans
Quantity 1
Diameter 910 mm
Speed 840 rpm
Power 2,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
BC/BD-191EB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
59.468 kW Fluid flow 10.32 m³/h Pressure drop 94.4 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
47.828 kW Fluid flow 8.30 m³/h Pressure drop 64.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 33.67 not rated not rated not rated not rated not rated
40 59.47 33.89 not rated not rated not rated not rated
45 84.79 59.58 34.09 not rated not rated not rated
50 109.96 84.81 59.70 34.28 not rated not rated
55 135.05 109.89 84.86 59.83 34.47 not rated
60 160.11 134.90 109.87 84.94 59.99 34.66

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 27.31 not rated not rated not rated not rated not rated
40 47.83 27.49 not rated not rated not rated not rated
45 67.90 47.92 27.66 not rated not rated not rated
50 87.83 67.91 48.01 27.81 not rated not rated
55 107.70 87.77 67.95 48.12 27.96 not rated
60 127.53 107.57 87.75 68.02 48.25 28.13

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 59.468 10.32 94.4
Low speed (Y) 47.828 8.30 64.2

Dimensions

Dimension drawing of BC/BD-191EB1-B04 C
Dimension drawing
Dimensions as drawn
A 1750 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 1500 mm
H 1400 mm
I 1190 mm
K 2050 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 2050 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.