BC/BD-t-363AC1-B01 C
99.16 kW
Defrost: None
Product code: BC/BD-191GD1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 25,813 m³/h |
|---|---|
| External surface | 411.6 m² |
| Inner volume | 47.8 dm³ |
| Fin material | Aluminium |
| Net weight | 327 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 90.6 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-191GD1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 59.00 | not rated | not rated | not rated | not rated | not rated |
| 40 | 99.13 | 59.06 | not rated | not rated | not rated | not rated |
| 45 | 138.13 | 98.85 | 59.12 | not rated | not rated | not rated |
| 50 | 176.75 | 137.56 | 98.63 | 59.19 | not rated | not rated |
| 55 | 215.19 | 175.90 | 137.09 | 98.49 | 59.30 | not rated |
| 60 | 253.53 | 214.06 | 175.19 | 136.75 | 98.44 | 59.44 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 45.87 | not rated | not rated | not rated | not rated | not rated |
| 40 | 76.20 | 45.91 | not rated | not rated | not rated | not rated |
| 45 | 105.58 | 75.98 | 45.95 | not rated | not rated | not rated |
| 50 | 134.63 | 105.13 | 75.80 | 46.01 | not rated | not rated |
| 55 | 163.54 | 133.97 | 104.76 | 75.69 | 46.10 | not rated |
| 60 | 192.37 | 162.68 | 133.43 | 104.51 | 75.68 | 46.25 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 99.126 | 17.19 | 66.9 |
| Low speed (Y) | 76.198 | 13.21 | 41.9 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 1190 mm |
| K | 3050 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3050 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.