BC/BD-t-2X180GB1-B01 C
93.56 kW
Defrost: None
Product code: BC/BD-191GD5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 26,246 m³/h |
|---|---|
| External surface | 348.0 m² |
| Inner volume | 47.8 dm³ |
| Fin material | Aluminium |
| Net weight | 317 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 90.4 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-191GD5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 55.20 | not rated | not rated | not rated | not rated | not rated |
| 40 | 93.56 | 55.29 | not rated | not rated | not rated | not rated |
| 45 | 130.92 | 93.37 | 55.37 | not rated | not rated | not rated |
| 50 | 167.95 | 130.46 | 93.20 | 55.46 | not rated | not rated |
| 55 | 204.83 | 167.25 | 130.09 | 93.09 | 55.57 | not rated |
| 60 | 241.62 | 203.89 | 166.66 | 129.81 | 93.07 | 55.74 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 43.55 | not rated | not rated | not rated | not rated | not rated |
| 40 | 73.05 | 43.61 | not rated | not rated | not rated | not rated |
| 45 | 101.70 | 72.88 | 43.68 | not rated | not rated | not rated |
| 50 | 130.07 | 101.33 | 72.75 | 43.75 | not rated | not rated |
| 55 | 158.31 | 129.51 | 101.03 | 72.68 | 43.84 | not rated |
| 60 | 186.47 | 157.56 | 129.05 | 100.83 | 72.68 | 43.99 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 93.562 | 16.24 | 60.5 |
| Low speed (Y) | 73.048 | 12.67 | 38.8 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 1190 mm |
| K | 3050 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3050 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.