BC/BD-t-2x180GC5-B03 C
59.70 kW
Defrost: None
Product code: BC/BD-191KC5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 23,284 m³/h |
|---|---|
| External surface | 122.6 m² |
| Inner volume | 17.3 dm³ |
| Fin material | Aluminium |
| Net weight | 213 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 91.4 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-191KC5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 34.00 | not rated | not rated | not rated | not rated | not rated |
| 40 | 59.72 | 34.23 | not rated | not rated | not rated | not rated |
| 45 | 84.90 | 59.83 | 34.44 | not rated | not rated | not rated |
| 50 | 109.91 | 84.92 | 59.95 | 34.63 | not rated | not rated |
| 55 | 134.84 | 109.85 | 84.97 | 60.08 | 34.82 | not rated |
| 60 | 159.74 | 134.70 | 109.83 | 85.05 | 60.24 | 35.02 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | not rated | not rated | not rated | not rated | not rated | not rated |
| 40 | not rated | not rated | not rated | not rated | not rated | not rated |
| 45 | not rated | not rated | not rated | not rated | not rated | not rated |
| 50 | not rated | not rated | not rated | not rated | not rated | not rated |
| 55 | not rated | not rated | not rated | not rated | not rated | not rated |
| 60 | not rated | not rated | not rated | not rated | not rated | 27.84 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 59.716 | 10.36 | 69.8 |
| Low speed (Y) | — | — | — |
| A | 1750 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1500 mm |
| H | 1400 mm |
| I | 1180 mm |
| K | 2050 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2050 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.